Product Safety Report: Kidde CO2 Klem Valve (2310-0089)
Product Safety Report for Kidde CO2 Klem Valve presenting a serious risk of injuries.
Product: Kidde CO2 Klem Valve
Hazard: The product presents a serious risk of injuries as the valve could detach and cause the discharge of CO2 gas and high velocity ejection of components of the valve.
Corrective action: Affected units were identified and stock withdrawn from the market. A safety notice has been issued to affected customers in the UK. The manufacturer has developed a safety guard that can be fitted over the top of the valve.
Product information
Type | Pressure Equipment / Vessels - CO2 Klem Valve End Cap |
---|---|
Brand | Kidde |
Affected Batches | 01/2022 to 05/2023 |
Additional Identifiers | Kidde CO2 Fire Suppression System incorporating Kidde CO2 Klem Valve |
Country of Origin | China |
Product Description | A CO2 fire suppression system including a cylinder assembly, a component of which is a fast-acting container valve (the Valve). |
Product Report and Image |
Hazard
The KIDDE Co2 Klem Valve end cap could accidently detach from the valve body on a Co2 cylinder assembly.
This can result in the unintended discharge of Co2 gas and the high velocity ejection of components of the valve
Corrective action
Affected units were identified and existing stock withdrawn from the market.
A Safety Notice was issued to the affected customers in the UK, warning customers of the risk, along with advisory control measures. The manufacturer will issue further communications as required.
The manufacturer has developed a safety guard that can be fitted over the top of the valve which should stop the ejection of any parts if a valve failed, along with instructions on how to install the guard safely.
Additional information
PSD case number: 2310-0089
Notified by: Health and Safety Executive